Text extracted from the exhibit documents filed with the FCC. Open a document above to read the original.
Lutron Electronics Co., Inc., 7200 Suter Road Coopersburg, PA 18036-1299 U.S.A. Test Link B Hold the indicated button on each transmitter for 6 seconds. The fixture will flash to show that wireless transmitters have been associated. To associate another transmitter, repeat steps 4A and 4B. A Initiate association mode on the Project 37 Control Module by shining a green laser pointer at the laser detection hole on the sensor until the load attached to the Project 37 Control Module starts flashing every 2 seconds. Alternatively, press and hold the toggle button for 6 seconds on the Project 37 Control Module to initiate association mode. 3 OR Laser Detection (smallest) Associate Wireless Transmitters to Project 37 Control Module Before beginning this step, make sure that there are no other Project 37 Control Modules being set up in the building which are currently in this association mode.. It is possible that wireless transmitters from other systems can be incorrectly associated to this module. Green laser specifications: • Wave output: constant • Wavelength: 532 nm • Output power: 5 mW maximum Technical Assistance | 1.800.523.9466 USA, Canada, and the Caribbean | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Others | www.lutron.com 041467 Rev. A 07/2014 Part of the Energi TriPak® Family Project 37 | Installation + For each fixture, ensure that you have: One Project 37 Control ModuleAt least one Sensor or Pico® Wireless ControlAt least one 0 – 10 V Fluorescent Ballast or LED Driver Required Components Project 37 Occupancy/Vacancy and Daylight Sensor (1 maximum) Pico® Wireless Control (10 maximum) 6 mA maximum for the control lines. Switches up to 1 A total. May be pre-installed in light fixture. Project 37 Control Module with 0 –10 V Raise Toggle Lower Load Status LED Consult third-party 0 – 10 V fixtures installation guide for fixture-specific wiring. Start Here + Wireless Controls OnAll lights 100% FavoriteAll lights 50% OffAll lights off Default Functionality English All Wireless Transmitters must be installed within 30 ft (9 m) of the Project 37 Control Module. Control: 0–10 V- 6 mA Important Notes: Please read before installing. For installation by a qualified electrician in accordance with all local and national electrical codes. • Note: Use copper conductors only. • Check to see that the device type and rating is suitable for the application. • DO NOT install if product has any visible damage. • If moisture or condensation is evident, allow the product to dry completely before installation. • Operate between 0 °C and 40 °C, ambient. • 0% to 90% humidity, non-condensing. • For indoor use only. 120 – 277 V~ 50 / 60 Hz 1 A FC-1 (Project 37 Control Module) UL 2043 Plenum Rated 12 V- 25 mA FC-0 (Project 37 Sensor) Sensor Pico® Wireless Control Project 37 Control Module 30 ft (9 m) max 40 ft (12 m) 30 ft (9 m) Project 37 Control Module 1 PIR Lens Laser Detection Daylight Lens Note: Project 37 Control Module can be used without a Sensor Install control module directly to fixture or in junction box nearest the fixture. Install sensor in ceiling near fixture so as to optimize cover- age in the desired area. Radio Powr SavrTM Occupancy/Vacancy Sensor (10 maximum) Install Project 37 Control Module and Sensor Suggested Installation Location: Close to the Fixture/Troffer. The Project 37 Control Module can be installed in a fixture/troffer, junction box or marshalling box using the conduit nut (provided) or with mounting screws (not provided). Please consult local and national electric codes for proper installation. If installing unit inside a junction box, please see Application Note #423 at www.lutron.com/TechnicalDocumentLibrary/048423.pdf B Ideally mount the sensor to the ceiling tile close to the fixture using the wire form or using the command strips (included). The 2 communication wires from the sensor attaches to the control module poke in connectors. C Once installed, energize the Project 37 Control Module. Green/Yellow Neutral Switched Hot/Live Violet Gray Fixture Earth + – To additional 0 – 10 V fixtures Hot (Black) Neutral + – NEUHOT Class 2 MAINS + – NEU HOT Class 2 MAINS Switched Hot (Red) Hot (Black) Neutral (White) Neutral Fixture/Troffer or Junction Box 1/2 in (21 mm) Knockout Opening Conduit Nut From back of sensor Violet Gray Fixture Earth Green/Yellow WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit breaker before installing the unit. Spring arms Note: For solid ceilings or others where the wireform cannot be utilized, use the supplied Command strips to adhere sensor to desired location on ceiling or fixture. Sensor Detection Range 2 Install the Sensor The Project 37 sensor mounts to the ceiling surface with a supplied wireform clip. Two wires connect to the control module and can either be routed through a hole in the ceiling or across the ceiling surface. DO NOT install on ceilings higher than 12 ft (3.7 m). The sensor should be installed in a location where it has a good view of the space that it is meant to cover. 15 ft (4.6 m) 9 ft (2.7 m) 3 ft (0.9 m) 03 ft (0.9 m) 9 ft (2.7 m) 15 ft (4.6 m) 400 ft 2 (37 m 2 ) maximum coverage area of one sensor when mounted on an 9 ft (2.75 m) ceiling Ceiling Floor 9 ft (2.75 m) 15 ft (4.6 m) 9 ft (2.7 m) 3 ft (0.9 m) 0 3 ft (0.9 m) 9 ft (2.7 m) 15 ft (4.6 m) 15 ft (4.6 m) 9 ft (2.7 m) 3 ft (0.9 m) 03 ft (0.9 m) 9 ft (2.7 m) 15 ft (4.6 m) A Slide closed end of wire form under the two retention arms on the back of the sensor B While continuing to push against the retention arms, rock the other side of the wireform down against the sensor and slide them into place under the loop retention features C Push wireform through tile and bend on the backside of the tile to complete the mounting. 041467 Rev. A 07/2014 Part of the Energi TriPakR Family Project 37 Load Control Module | Programming ALL PROGRAMMING IS OPTIONAL Programming is not required for default functionality • Set a favorite light level • Set …
Text truncated - open the document above for the full version.
FCC CFR47 PART 15 SUBPART C INDUSTRY CANADA RSS-210 ISSUE 8 CERTIFICATION TEST REPORT FOR CONTROLLER MODEL NUMBER: FC-1 & FC-2 FCC ID: JPZ0108 IC: 2851A-JPZ0108 REPORT NUMBER: 10382159 ISSUE DATE: 2014-08-15 Prepared for LUTRON ELECTRONICS CO., INC. 7200 SUTER ROAD COOPERSBURG PA, 18036, USA Prepared by UL LLC 1285 WALT WHITMAN RD. MELVILLE, NY 11747, U.S.A. TEL: (631) 271-6200 FAX: (877) 854-3577 REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 2 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. Revision History Rev. Issue Date Revisions Revised By -- 8/15/14 Initial Issue M. Antola REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 3 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. TABLE OF CONTENTS 1. ATTESTATION OF TEST RESULTS ................................................................................. 4 2. TEST METHODOLOGY ..................................................................................................... 5 3. FACILITIES AND ACCREDITATION ................................................................................. 5 4. CALIBRATION AND UNCERTAINTY ................................................................................ 5 4.1. MEASURING INSTRUMENT CALIBRATION .............................................................. 5 4.2. SAMPLE CALCULATION ............................................................................................ 5 4.3. MEASUREMENT UNCERTAINTY ............................................................................... 5 5. EQUIPMENT UNDER TEST ............................................................................................... 6 5.1. DESCRIPTION OF EUT .............................................................................................. 6 5.2. DESCRIPTION OF AVAILABLE ANTENNAS .............................................................. 6 5.3. SOFTWARE AND FIRMWARE .................................................................................... 6 5.4. WORST-CASE CONFIGURATION AND MODE .......................................................... 6 5.5. MODIFICATIONS ........................................................................................................ 6 5.6. DESCRIPTION OF TEST SETUP ................................................................................ 7 6. TEST AND MEASUREMENT EQUIPMENT ....................................................................... 9 7. ANTENNA PORT TEST RESULTS ...................................................................................11 7.1. 20 dB AND 99% BW ...................................................................................................11 7.2. DUTY CYCLE .............................................................................................................15 7.3. TRANSMISSION TIME ...............................................................................................19 8. RADIATED EMISSION TEST RESULTS...........................................................................20 8.1. TX RADIATED SPURIOUS EMISSION ......................................................................20 8.2. RX RADIATED SPURIOUS EMISSION ......................................................................28 9. AC MAINS LINE CONDUCTED EMISSIONS ....................................................................33 10. SETUP PHOTOS ...........................................................................................................46 REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 4 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. 1. ATTESTATION OF TEST RESULTS COMPANY NAME: LUTRON ELECTRONICS CO., INC. 7200 SUTER ROAD COOPERSBURG, PA, 18036, USA EUT DESCRIPTION: CONTROLLER MODEL: FC-1 & FC-2 SERIAL NUMBER: NON-SERIALIZED PRODUCTION UNIT DATE TESTED: 8/6/14 – 8/14/14 APPLICABLE STANDARDS STANDARD TEST RESULTS FCC PART 15 SUBPART C Pass INDUSTRY CANADA RSS-210 Issue 8, Annex 1 Pass INDUSTRY CANADA RSS-GEN Issue 3 Pass UL LLC tested the above equipment in accordance with the requirements set forth in the above standards, using test results reported in the test report documents referenced below and/or documentation furnished by the applicant. All indications of Pass/Fail in this report are opinions expressed by UL LLC based on interpretations of these calculations. The results show that the equipment is capable of demonstrating compliance with the requirements as documented in this report. Note: The results documented in this report apply only to the tested sample, under the conditions and modes of operation, as described by the referenced documents. This document may not be altered or revised in any way unless done so by UL LLC and all revisions are duly noted in the revisions section. Any alteration of this document not carried out by UL LLC will constitute fraud and shall nullify the document. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, any agency of the Federal Government, or any agency of any government. Approved & Released For UL By: Tested By: Bob DeLisi Mike Antola Program Manager Project Lead UL LLC UL LLC REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 5 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written appr…
Text truncated - open the document above for the full version.
REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 46 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. 10. SETUP PHOTOS ANTENNA PORT ANTENNA PORT REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 47 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. RADIATED EMISSION FOR PORTABLE CONFIGURATION – X ORIENTATION RADIATED EMISSION FOR PORTABLE CONFIGURATION – X ORIENTATION REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 48 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. RADIATED EMISSION FOR PORTABLE CONFIGURATION – Y ORIENTATION RADIATED EMISSION FOR PORTABLE CONFIGURATION – Y ORIENTATION REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 49 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. RADIATED EMISSION FOR PORTABLE CONFIGURATION – Z ORIENTATION RADIATED EMISSION FOR PORTABLE CONFIGURATION – Z ORIENTATION REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 50 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. RADIATED EMISSION BELOW 1000 MHz RADIATED EMISSIONS BELOW 1000MHz (FRONT) REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 51 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. RADIATED EMISSIONS BELOW 1000MHz (BACK) REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 52 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. RADIATED EMISSION ABOVE 1000 MHz RADIATED EMISSIONS ABOVE 1000 MHz (FRONT) REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 53 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. RADIATED EMISSIONS ABOVE 1000 MHz (BACK) REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 54 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. AC MAINS LINE CONDUCTED EMISSION LINE CONDUCTED EMISSION (FRONT) REPORT NO: 100382159 DATE: 2014-08-15 FCC ID: JPZ0108 IC: 2851A-JPZ0108 Page 55 of 55 UL LLC. FORM NO: CCSUP4701D 1285 WALT WHITMAN RD, MELVILLE, NY 11747, USA TEL: (631) 271-6200 FAX: (877) 854-3577 This report shall not be reproduced except in full, without the written approval of UL LLC. END OF REPORT LINE CONDUCTED EMISSION (BACK)
| # | Rule Parts | Frequency Range | Power Output |
|---|---|---|---|
| 1 | 15C | 431 MHz - 437 MHz | - |
Wireless Interface
Equipment Class
DTS - Digital Transmission SystemWireless Processor
Equipment Class
DTS - Digital Transmission SystemCopy of Wireless Processor
Equipment Class
DTS - Digital Transmission SystemLED Downlight
Equipment Class
DTS - Digital Transmission SystemLED Lighting Controller
Equipment Class
DTS - Digital Transmission System