1 G1100 WirelessHART Smart Gateway User Manual V2.2 http://www.microcyber.cn II WirelessHART Smart Gateway G1100 Caution In order to ensure the personal and property safety, and get the best product experience, before using, installation, and maintenance products, please be sure to read all the content of the document. Security Reminder The user must pay special attention to the content of this manual to ensure that the personal and property safety. The potential security problems may cause are marked with orange color. Please refer to the safety information before operations marked with that color. Warning The products described in the manual are not designed for nuclear industry application. http://www.microcyber.cn II 1 Overview ................................................................................................................................... 1 1.1 Brief Introduction ................................................................................................................ 1 1.2 Including Goods .................................................................................................................. 1 2 First Connection ........................................................................................................................ 2 2.1Summary ............................................................................................................................. 2 2.2 System Requirements ......................................................................................................... 3 2.3 First Setting ......................................................................................................................... 3 2.3.1 Prepare PC/Portable Computer ............................................................................... 3 2.3.2 Connection and Power On ....................................................................................... 4 2.3.3 Gateway Configuration ............................................................................................ 4 3 Installation and Connection ...................................................................................................... 8 3.1 Summary ............................................................................................................................. 8 3.1.1 General Considerations ............................................................................................ 8 3.1.2 Physical Description ................................................................................................. 8 3.2 Installation .......................................................................................................................... 8 3.3 Remote Antenna (optional) .............................................................................................. 10 3.4 Connection ........................................................................................................................ 13 3.4.1 Ground ................................................................................................................... 13 3.4.2 Ethernet ................................................................................................................. 14 3.3.3RS-485 ..................................................................................................................... 14 3.3.4 Power ..................................................................................................................... 14 4 PC Integration ......................................................................................................................... 16 4.1 Summary ........................................................................................................................... 16 4.2 Network Structure ............................................................................................................ 16 4.3 Modbus ............................................................................................................................. 17 4.3.1 Communication Setting .......................................................................................... 17 4.3.2 Register Map .......................................................................................................... 18 4.4 Private Protocol ................................................................................................................. 21 4.4.1 Active Upload Protocol .......................................................................................... 21 4.4.2 Downward Communication Protocol ..................................................................... 22 4.5 OPC .................................................................................................................................... 24 4.5.1 Software Installation and Usage ............................................................................ 24 4.5.2 OPC Mapping ......................................................................................................... 26 4.6 HART-IP .............................................................................................................................. 27 5 Failure Solution ....................................................................................................................... 28 6 Function .................................................................................................................................. 31 6.1Language Selection ........................................................................................................... 31 6.2 Network Information ........................................................................................................ 32 6.2.1 Network Overview ................................................................................................. 32 6.2.2 Node Information .............................................................…
Text truncated - open the document above for the full version.
C5266091_X8_Ed.1 1/1 Letter of Authorization Company: Microcyber Corporation Address: FLOOR 1-3, 1#, NO.17-8, WENSU STREET, HUNNAN NEW DISTRICT, SHENYANG, LIAONING, P.R.C. Product Name: G1100 WirelessHART Smart Gateway Model Number: G1100 FCC Identifier: 2ADYAG1100 We authorize LGAI Technological Center S.A., Ronda de la Font delCarme, s/n, 08193 Bellaterra, Spain, to act on our behalf on all matters concerning the above named equipment. Any individual within LGAI Technological Center S.A. is authorized to act on our behalf and take action on the application. We declare that authorize LGAI Technological Center S.A., Ronda de la Font del Carme, s/n, 08193 Bellaterra, Spain, is allowed to forward all information related to the approval project to the Federal Communication Commission and to discuss any issues concerning the approval application. Any and all acts carried out by LGAI Technological Center S.A. on our behalf shall have the same effect as acts of our own. Name: Yong Li Date: 2022.05.18 Title: Product Manager Signature of applicant:
C5266091_X10_Ed.2 1/1 < Microcyber Corporation > Office of Engineering Technology Federal Communications Commission 7435 Oakland Mills Road Columbia, MD 21046 Date: 2022.04.10 Subject: Request for Confidentiality FCC ID: 2ADYAG1100 To Whom It May Concern, Pursuant to the provisions of Sections 0.457 and 0.459 of Commission's rules (47CFR0.457, 0.459), we are requesting the Commission to withhold the following attachment(s) as confidential document from public disclosure. Exhibits Long-Term Confidentiality Short-Term Confidentiality NOTE 2 ID Label/Location No No Attestation Statement No No External Photos No ☐ Block Diagram ☒ ☐ Schematics ☒ ☐ Test Report No No Test Setup Photos No ☐ User’s Manual ☐ NOTE 1 ☐ Internal Photos ☐ NOTE 1 ☐ Parts List / Tune Up ☐ ☐ RF Exposure Info No No Operational Description ☒ ☐ Cover Letter(s) No No SDR Software / Security Info ☐ No NOTE 1: Long-Term Confidentiality may be permitted under special conditions (See II. LONG-TERM CONFIDENTIALITY, Section 3 of KDB 726920, use last in force) NOTE 2: Short-Term Confidentiality can be requested for a maximum of 180 days from the date of the grant. Above mentioned document contains detailed system and equipment description are considered as proprietary information in operation of the equipment. The public disclosure of above documents might be harmful to our company and would give competitor an unfair advantage in the market. In case of short-term Confidentiality, the applicant requests the exhibits selected above are withheld from public view for a period of ______ days from the date of the Grant of Equipment Authorization and prior to marketing. It is our understanding that all measurement test reports, FCC ID label format and correspondent during certification review process cannot be granted as confidential documents and those information will be available for public review once the grant of equipment authorization is issued. C5266091_X10_Ed.2 1/1 Sincerely, Signature: Name: Yong Li Title: Product Manager
External Photo FCC ID: 2ADYAG1100 IC:28548-G1100
Lable location
Internal Photo FCC ID: 2ADYAG1100 IC:28548-G1100 ANT
FCC ID : 2ADYAG1100 RF EXPOSURE EVALUATION According to FCC 1.1310: The criteria listed in the following table shall be used to evaluate the environment impact of human exposure to radio frequency (RF) Radiation as specified in §1.1307(b) Limits for Maximum Permissible Exposure (MPE) Frequency Range(MHz) Electric Field Strength(V/m) Magnetic Field Strength(A/m) Power Density(mW/cm 2 ) Average Time (A) Limits for Occupational/Control Exposures 300-1500 -- -- F/300 6 1500-100000 -- -- 5 6 (B) Limits for General Population/Uncontrol Exposures 300-1500 -- -- F/1500 6 1500-100000 -- -- 1 30 11.1 Friis transmission formula: Pd= (Pout*G)\ (4*pi*R 2 ) Where Pd= Power density in mW/cm 2 Pout=output power to antenna in mW G= Numeric gain of the antenna relative to isotropic antenna Pi=3.1416 R= distance between observation point and center of the radiator in cm Pd the limit of MPE, 1mW/cm 2 ,If we know the maximum gain of the nd total power input to the antenna, through the calculation, we will know the distance where the MPE limit is reached. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body. 11.2 Measurement Result 2.4G ISM Band Antenna gain: 2 dBi modulation Channel Freq. (MHz) Measured power (dBm) Tune-up power (dBm) Max tune-up power (dBm) Antenna Gain Numeric Evaluation result (mW/cm2 ) Power density Limits (mW/cm2 ) DSSS 2405 7.23 7 to 8 8 1.58 0.001989 1 2440 6.63 6 to 7 7 1.58 0.001580 1 2475 5.63 5 to 6 6 1.58 0.001255 1 Therefore the worst-case situation is 0.001989, which is less than “1”, This confirmed that the device comply with FCC 1.1310 MPE limit.
Page 1 of 36 Address:No.11,WuSongRoad, Tel: 86-769-22607797 DongchengDistrict,Dongguan, Fax: 86-769-22607907 GuangdongProvince,China523117 http://www.cpcteam.com FCC 47 CFR PART 15 SUBPART C TEST REPORT Report Number. ..................... : 90267-22-72-22-PP005 Date of issue .......................... : May.16.2022 Tested by (+signature) .......... : Duke Approved by (+signature) .... : Jason Testing Laboratory name ..... : SLG-CPC Testlaboratory Co., Ltd. Address .................................. : No. 11, Wu Song Road, Dongcheng District, Dongguan, Guangdong Province, China 523117 Applicant’s name ................... : Microcyber Corporation Address .................................. : FLOOR 1-3, 1#, NO.17-8, WENSU STREET, HUNNAN NEW DISTRICT, SHENYANG, LIAONING, P.R.C. Manufacturer’s name .......... : Microcyber Corporation Address .................................. : FLOOR 1-3, 1#, NO.17-8, WENSU STREET, HUNNAN NEW DISTRICT, SHENYANG, LIAONING, P.R.C. Factory’s name .................... : Microcyber Corporation Address .................................. : FLOOR 1-3, 1#, NO.17-8, WENSU STREET, HUNNAN NEW DISTRICT, SHENYANG, LIAONING, P.R.C. Standard(s) ............................ : FCC 47 CFR Part 2, Subpart J FCC 47 CFR Part 15, Subpart C Test item description ............ : G1100 WirelessHART Smart Gateway Trade Mark ............................. : Model/Type reference ........... : G1100 FCC ID..................................... : 2ADYAG1100 Date of receipt of test item ... : Apr.20.2022 Date (s) of performance of test .......................................... : Apr.21.2022 to May.12.2022 Summary of Test Results ..... : Pass The Summary of Test Results based on a technical opinion belongs to the standard(s). General disclaimer: This report shall not be reproduced except in full, without the written approval of SLG-CPC Testlab oratory Co., Ltd. The test results in the report only apply to the tested sample. 90267-22-72-22-PP005 Page 2 of 36 Address:No.11,WuSongRoad, Tel: 86-769-22607797 DongchengDistrict,Dongguan, Fax: 86-769-22607907 GuangdongProvince,China523117 http://www.cpcteam.com TABLE OF CONTENTS 1 EUT TECHNICAL DESCRIPTION ..................................................................................................... 4 2 SUMMARY OF TEST RESULT ......................................................................................................... 5 3 TEST METHODOLOGY ..................................................................................................................... 6 3.1 GENERAL DESCRIPTION OF APPLIED STANDARDS ............................................................. 6 3.2 MEASUREMENT EQUIPMENT USED ....................................................................................... 6 3.3 DESCRIPTION OF TEST MODES .............................................................................................. 7 4 FACILITIES AND ACCREDITATIONS .............................................................................................. 8 4.1 FACILITIES ................................................................................................................................. 8 4.2 LABORATORY ACCREDITATIONS AND LISTINGS .................................................................. 8 5 TEST SYSTEM UNCERTAINTY ........................................................................................................ 9 6 SETUP OF EQUIPMENT UNDER TEST ......................................................................................... 10 6.1 RADIO FREQUENCY TEST SETUP 1 ...................................................................................... 10 6.2 RADIO FREQUENCY TEST SETUP 2 ...................................................................................... 10 6.3 CONDUCTED EMISSION TEST SETUP .................................................................................. 12 6.4 BLOCK DIAGRAM CONFIGURATION OF TEST SYSTEM...................................................... 13 6.5 SUPPORT EQUIPMENT ........................................................................................................... 13 7 TEST REQUIREMENTS .................................................................................................................. 14 7.1 DTS (6DB) BANDWIDTH .......................................................................................................... 14 7.2 MAXIMUM PEAK CONDUCTED OUTPUT POWER ................................................................ 17 7.3 MAXIMUM POWER SPECTRAL DENSITY .............................................................................. 18 7.4 UNWANTED EMISSIONS IN NON-RESTRICTED FREQUENCY BANDS .............................. 21 7.5 RADIATED SPURIOUS EMISSION .......................................................................................... 27 7.6 CONDUCTED EMISSIONS TEST ............................................................................................ 35 7.7 ANTENNA APPLICATION ......................................................................................................... 36 90267-22-72-22-PP005 Page 3 of 36 Address:No.11,WuSongRoad, Tel: 86-769-22607797 DongchengDistrict,Dongguan, Fax: 86-769-22607907 GuangdongProvince,China523117 http://www.cpcteam.com Modified Information Version Report No. Revision Data Summary Ver.1.0 90267-22-72-22-PP001 / Original Version Ver.1.1 90267-22-72-22-PP005 2022.06.08 This report is based on 90267-22-72-22-PP001 Modify the trademark 90267-22-72-22-PP005 Page 4 of 36 Address:No.11,WuSongRoad, Tel: 86-769-22607797 DongchengDistrict,Dongguan, Fax: 86-769-22607907 GuangdongProvince,China523117 http://www.cpcteam.com 1 EUT TECHNICAL DESCRIPTION Characteristics Description Device Type: 2.4G ISM Band Model Number: G1100 Modulation: DSSS Operating Frequency Range(s): 2405-2475MHz Number of Channels: 15 Channels Channel Separation: 5MHz Transmit Power Max: 7.23 dBm Antenna Type : Omni-directional Ant…
Text truncated - open the document above for the full version.
Setup Photo FCC ID: 2ADYAG1100 IC:28548-G1100
| # | Rule Parts | Frequency Range | Power Output |
|---|---|---|---|
| 1 | 15C | 2.40 GHz - 2.48 GHz | 5.28 mW |

WirelessHart module
Equipment Class
DTS - Digital Transmission System