90 30 kW Wireless Charging System User Manual and Professional Installation Guide User Manual – 30kW WCS Model. No: M∞V air 30 Page: 2/100 Issued Date: 03.01.2024 Rev. 0.0 LEGAL INFORMATION This manual applies to the Wireless Charging System (WCS 30kW). Delta manuals undergo continuous revision in order to provide user with complete information regarding the installation and operation of WCS. Therefore, before starting installation work, always consult Delta to check whether a newer version of the User Manual is available. This manual is intended for use by electrical installers who are competent for installation and commissioning of grid-connected electrical systems/products. The information in this manual should be treated as confidential and no part of this manual may be reproduced without prior written permission from Delta. The information in this manual may not be used for any other purpose, directly connected to the use of the WCS. All translations of this manual that are not authorized by Delta Energy System (Germany) must be marked with the words "Translation of the original operating instructions." © Copyright – Delta Energy Systems (Germany) – All rights reserved. Delta Energy Systems Tscheulinstraße 21 79331 Teningen Germany User Manual – 30kW WCS Model. No: M∞V air 30 Page: 3/100 Issued Date: 03.01.2024 Rev. 0.0 Revision Record Revision Date Description 0.0 03.01.2024 First Release User Manual – 30kW WCS Model. No: M∞V air 30 Page: 4/100 Issued Date: 03.01.2024 Rev. 0.0 Table of Contents SECTION TITLE PAGE 1 Introduction ................................................................................................. 12 1.1 Purpose of this Document ........................................................................... 12 1.2 Target Audience ........................................................................................... 12 1.2.1 Access to the System ..................................................................................... 13 1.3 Scope of Supply ........................................................................................... 13 1.4 Intended Use ................................................................................................ 14 1.5 References ................................................................................................... 14 1.5.1 Delta Documentation ...................................................................................... 14 1.5.2 Open Source License & Credits ..................................................................... 14 1.6 Exclusion of Liability ..................................................................................... 15 2 Safety & Regulations ................................................................................... 16 2.1 Safety Symbols ............................................................................................ 16 2.2 Warning & Other Signs ................................................................................. 16 2.3 Labels............................................................................................................ 17 2.4 Safety Instructions ....................................................................................... 18 2.4.1 General Safety Instructions ............................................................................ 18 2.4.2 EMF Safety Instructions.................................................................................. 19 2.5 Regulatory Compliances ............................................................................. 24 2.5.1 EU ..................................................................................................................... 24 2.5.2 FCC ................................................................................................................... 25 2.5.3 ISED ................................................................................................................... 25 2.5.4 Miscellaneous .................................................................................................. 25 3 System Description & Operation ................................................................ 26 3.1 Overview ...................................................................................................... 26 3.1.1 Identification of WCS Subsystems ................................................................26 3.1.2 Wireless Charging ........................................................................................... 27 3.1.3 Models, Variants & Interoperability ............................................................... 28 3.2 Subsystem Description ............................................................................... 29 3.2.1 WPB ...................................................................................................................29 3.2.2 WPP .................................................................................................................. 39 3.2.3 WSU .................................................................................................................. 41 3.3 System Performance................................................................................... 45 3.3.1 Output Power and De-rating ......................................................................... 45 3.3.2 Efficiency and Losses .....................................................................................50 3.4 System Control Modes ................................................................................ 51 3.4.1 External Commanded CANopen® ................................................................. 51 3.4.2 External Commanded Ethernet (Not Implemented) .................................... 51 User Manual – 30kW WCS Model. No: M∞V air 30 Page: 5/100 Issued Date: 03.01.2024 Rev. 0.0 Table of Contents (Cont.) SECTION TITLE PAGE 3.5 Communications ................................................…
Text truncated - open the document above for the full version.
ATTENTION: U.S. Agent Designation for Service of Process Federal Communications Commission Authorization and Evaluation Division 7435 Oakland Mills Road Columbia, MD 21046 USA REGARDING: FCC Ce1iification - Section 2.911 (d)(7) Information Designated U .S. Agent Company Name: Approve-IT, Inc. Contact Name: Nathan Grinager Sh·eet Address: 8011 34 th Ave South, Suite 342 City/Province/Zip: Bloomington, MN 55425 T elephone No: 651-247-1678 Email: [email protected] FRN #: 0027533835 This letter is t o confirm that we ("the Designated U.S. Agent) have accepted the responsibility to act as the Designated U.S. Agent for Service of Process as required by section 47 CFR 2.91 l(d)(7) on behalfofthe Applicant noted below. U.S. Agent Signature: Date: October 6, 2023 S igned by (Printed Name/Title): Nathan Grinager / Co-President *This letter is valid indefinitely for all applications submitted within the period of 07/26/2023 - 07/25/2024. The Applicant confirms its explicit consent and acknowledges that they must maintain an agent for no less than one year after terminating all marketing and impo1iation OR the conclusion of any Commission-related proceeding involving the equipment. The applicant further acknowledges their responsibility to inform the FCC wh enever the Designated U.S. Agent information above changes. Applicant Company name: DELTA ENERGY SYSTEM (GERMANY) GmbH Grnntee Code: 2AVWK Grantee FRN #: 0029327780 Contact Name: Dominique Hessmann Street Address: Tscheulinsh·. 21 City/Province/Zip: Teningen/Baden Wtirttemberg/79331 Te lephone No: +49 7641 455315 Email: [email protected] Applicant Signature: . 11 .A • V, Date: 06.10.2023 Signed by (Printed Name/Title): Dominique Hessmann DEL TA ENERGY SYSTEMS (GERMANY) GMBH Teningen Site 0 Tscheulinstr. 21. 79331 TENINGEN. GERMANY, Tel. + 49 7641 455 o. Fax + 49 7641 455 318 0 Managing Director: Dr. Peter Ide; Andreas Kostrzewa; Dalip Sharma 0 Commerzbank AG. Swift Code DRESDEFF445. IBAN: DE48440800500399982800. Bank Account: 0399982800, Bank No.: 44080050 0 VAT No: DE 811249878; Tax-No.: 343 5703 2027 DE; Registr. Office: Arnsberg HRB 5717 www.deltaenergysystems.com Reg.-Nr.: 00023 Seite 1 von 1
SIQ Ljubljana, Mašera-Spasićeva ulica 10, SI-1000 Ljubljana, Slovenia T +386 1 4778 100, F +386 1 4778 444, [email protected], www.siq.si External photos Project file: C20221443 Date: 2023-03-23 Pages: 10 Product: Wireless charger - Primary Box and Primary Pad Type reference: EOE18010815, EOE18010851 Page: 2 (10) Figure 1: Primary Box Page: 3 (10) Figure 2: Primary Box Figure 3: Primary Box Page: 4 (10) Figure 4: Primary Box Page: 5 (10) Figure 5: Primary Box Page: 6 (10) Figure 6: Primary Box Figure 7: Primary Pad Page: 7 (10) Figure 8: Primary Pad Figure 9: Primary Pad Page: 8 (10) Figure 10: Primary Pad Page: 9 (10) Figure 11: Primary Pad Page: 10 (10)
A4 THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF DELTA ENERGY SYSTEMS (GERMANY) GMBH AND SHALL NOT BE REPRODUCED OR USED AS THE BASIS FOR THE MANUFACTURE OR SELL OF APPARATUSES OR DEVICES WITHOUT PERMISSION. Description Part No.: Delta Energy Systems (Germany) GmbH c Plant Teningen Sheet: SIZE Rev.:Description:Date:Drawn:Checked: Approved: 00FIRST RELEASE10.Feb.20 DELANGT 10.Feb.20 DELANGT 10.Feb.20 DEKOENM 10.Feb.20 01UPDATE VIEWS TO P1.118.May. 2020 DELANGT 18.May. 2020 DELANGT 18.May. 2020 DEKOENM 18.May. 2020 02Release P2 25.Jun.2021 DELANGT 25.Jun.2021 DELANGT 25.Jun.2021 DEKOENM 25.Jun.2021 03 UPDATE VIEWS; NEW LED LABEL (POS50) 17.Jan.22 delangt 17.Jan.22 delangt 17.Jan.22 dekoenm 17.Jan.22 03 1 of 2Ver.:03.2 EOE18010851Used on: EOE18010851 SN0 REV.: Doc-Typ: CS WPP STD 30KW A B C D E B C D 1234567891011 Must meet Delta General Spec. 10000-0162 A2 THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF DELTA ENERGY SYSTEMS (GERMANY) GMBH AND SHALL NOT BE REPRODUCED OR USED AS THE BASIS FOR THE MANUFACTURE OR SELL OF APPARATUSES OR DEVICES WITHOUT PERMISSION. Sheet Description Part No.: FIRST ANGLE PROJECTION SIZE ECO_No.: Delta Energy Systems (Germany) GmbH c Plant Teningen 03 101BTE051742 of 2EOE18010851 Used on: MMUNIT:1:5SCALE: EOE18010851SN0 Doc-Typ: GENERAL TOL.: REV.: CS WPP STD 30KW 03.2Ver.:Released 17.Jan.2022DATE:dekoenmAPPROVED: 17.Jan.2022DATE:delangtCHECKED: 17.Jan.2022DATE:delangtDRAWN: 010 020 040 040 Part 1 Part 2 030 050
12345678 A B C D E F Must meet Delta General Spec. 10000-0162 A3 FRAME_NAME: DFU-MEA3H-2R00.frm THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF DELTA ENERGY SYSTEMS (GERMANY) GMBH AND SHALL NOT BE REPRODUCED OR USED AS THE BASIS FOR THE MANUFACTURE OR SELL OF APPARATUSES OR DEVICES WITHOUT PERMISSION. Sheet Description Part No.: FIRST ANGLE PROJECTION SIZE ECO_No.: Delta Energy Systems (Germany) GmbH c 03 101MTE000442 of 4EOE18010815 Used on: MMUNIT:2:1SCALE: 3268927903000 Doc-Typ: DINISO 2768-mHGENERAL TOL.: REV.: LABEL SPEC PLE 70*135 T0.07 EOE18010815 03.7Ver.:In Work 28.Jul.2022DATE:dekoenmAPPROVED: 28.Jul.2022DATE:delangtCHECKED: 28.Jul.2022DATE:delangtDRAWN: NOTES: 1) LLL = Location code MMM = number of Project (last three digits of project number) CC = Country code XX = use SAP revision YY = Year WW = Week ZZZZZZ = Serial number 2) 2D-Barcode type: DataMatrix ECC200 2D-Barcode text: EOE18010815 LLL XX YYWW ZZZZZZ 3) PRINTING MUST MEET TEST STANDARD IEC 62368-1 Ed.3- F3.10 (TEST FOR PERMANENCE MARKING) 4) Released thermal transfer ribbon: Ricoh B110CR and ARMOR AXR 7+ 5) Placement see page 3 6) Photomaster see page 4 7) Font = Arial 8) Raw Label = 3263789600 (PLE T0.17) PRELIMINARY 2) 12345678 A B C D E F Must meet Delta General Spec. 10000-0162 A3 FRAME_NAME: DFU-MEA3H-2R00.frm THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF DELTA ENERGY SYSTEMS (GERMANY) GMBH AND SHALL NOT BE REPRODUCED OR USED AS THE BASIS FOR THE MANUFACTURE OR SELL OF APPARATUSES OR DEVICES WITHOUT PERMISSION. Sheet Description Part No.: FIRST ANGLE PROJECTION SIZE ECO_No.: Delta Energy Systems (Germany) GmbH c 8 40 52 17 6 17 31 46 1 2 43 2.5 2.5 35 2 2 (1.5) 9 10 2 17 2 (1) 1.5 1 6 03 101MTE000443 of 4EOE18010815 Used on: MMUNIT:2:1SCALE: 3268927903000 Doc-Typ: DINISO 2768-mHGENERAL TOL.: REV.: LABEL SPEC PLE 70*135 T0.07 EOE18010815 03.7Ver.:In Work 28.Jul.2022DATE:dekoenmAPPROVED: 28.Jul.2022DATE:delangtCHECKED: 28.Jul.2022DATE:delangtDRAWN: PRELIMINARY 12345678 A B C D E F Must meet Delta General Spec. 10000-0162 A3 FRAME_NAME: DFU-MEA3H-2R00.frm THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF DELTA ENERGY SYSTEMS (GERMANY) GMBH AND SHALL NOT BE REPRODUCED OR USED AS THE BASIS FOR THE MANUFACTURE OR SELL OF APPARATUSES OR DEVICES WITHOUT PERMISSION. Sheet Description Part No.: FIRST ANGLE PROJECTION SIZE ECO_No.: Delta Energy Systems (Germany) GmbH c 03 101MTE000444 of 4EOE18010815 Used on: MMUNIT:2:1SCALE: 3268927903000 Doc-Typ: DINISO 2768-mHGENERAL TOL.: REV.: LABEL SPEC PLE 70*135 T0.07 EOE18010815 03.7Ver.:In Work 28.Jul.2022DATE:dekoenmAPPROVED: 28.Jul.2022DATE:delangtCHECKED: 28.Jul.2022DATE:delangtDRAWN: PRELIMINARY
12345678 A B C D E F Must meet Delta General Spec. 10000-0162 A3 FRAME_NAME: DFU-MEA3H-2R00.frm THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF DELTA ENERGY SYSTEMS (GERMANY) GMBH AND SHALL NOT BE REPRODUCED OR USED AS THE BASIS FOR THE MANUFACTURE OR SELL OF APPARATUSES OR DEVICES WITHOUT PERMISSION. Sheet Description Part No.: FIRST ANGLE PROJECTION SIZE ECO_No.: Delta Energy Systems (Germany) GmbH c 02 101MTE000452 of 4EOE18010851 Used on: MMUNIT:2:1SCALE: 3268957002000 Doc-Typ: DINISO 2768-mHGENERAL TOL.: REV.: LABEL SPEC PLE 40*52 T0.07 EOE18010851 02.6Ver.:In Work 28.Jul.2022DATE:dekoenmAPPROVED: 28.Jul.2022DATE:delangtCHECKED: 28.Jul.2022DATE:delangtDRAWN: NOTES: 1) LLL = Location code MMM = number of Project (last three digits of project number) CC = Country code XX = use SAP revision YY = Year WW = Week ZZZZZZ = Serial number 2) 2D-Barcode type: DataMatrix ECC200 2D-Barcode text: EOE18010851 LLL XX YYWW ZZZZZZ 3) PRINTING MUST MEET TEST STANDARD IEC 62368-1 Ed.3- F3.10 (TEST FOR PERMANENCE MARKING) 4) Released thermal transfer ribbon: Ricoh B110CR and ARMOR AXR 7+ 5) Placement see page 3 6) Photomaster see page 4 7) Font = Arial 8) Raw Label = 3263789600 (PLE T0.07) PRELIMINARY 2) 12345678 A B C D E F Must meet Delta General Spec. 10000-0162 A3 FRAME_NAME: DFU-MEA3H-2R00.frm THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF DELTA ENERGY SYSTEMS (GERMANY) GMBH AND SHALL NOT BE REPRODUCED OR USED AS THE BASIS FOR THE MANUFACTURE OR SELL OF APPARATUSES OR DEVICES WITHOUT PERMISSION. Sheet Description Part No.: FIRST ANGLE PROJECTION SIZE ECO_No.: Delta Energy Systems (Germany) GmbH c 40 52 46 5 9 17 6 6 31 8 17 1 2 43 2.5 2.5 35 2 (1.5) 2 10 (1) 1.5 1 1 02 101MTE000453 of 4EOE18010851 Used on: MMUNIT:2:1SCALE: 3268957002000 Doc-Typ: DINISO 2768-mHGENERAL TOL.: REV.: LABEL SPEC PLE 40*52 T0.07 EOE18010851 02.6Ver.:In Work 28.Jul.2022DATE:dekoenmAPPROVED: 28.Jul.2022DATE:delangtCHECKED: 28.Jul.2022DATE:delangtDRAWN: PRELIMINARY 12345678 A B C D E F Must meet Delta General Spec. 10000-0162 A3 FRAME_NAME: DFU-MEA3H-2R00.frm THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF DELTA ENERGY SYSTEMS (GERMANY) GMBH AND SHALL NOT BE REPRODUCED OR USED AS THE BASIS FOR THE MANUFACTURE OR SELL OF APPARATUSES OR DEVICES WITHOUT PERMISSION. Sheet Description Part No.: FIRST ANGLE PROJECTION SIZE ECO_No.: Delta Energy Systems (Germany) GmbH c 02 101MTE000454 of 4EOE18010851 Used on: MMUNIT:2:1SCALE: 3268957002000 Doc-Typ: DINISO 2768-mHGENERAL TOL.: REV.: LABEL SPEC PLE 40*52 T0.07 EOE18010851 02.6Ver.:In Work 28.Jul.2022DATE:dekoenmAPPROVED: 28.Jul.2022DATE:delangtCHECKED: 28.Jul.2022DATE:delangtDRAWN: PRELIMINARY
SIQ Ljubljana, Mašera-Spasićeva ulica 10, SI-1000 Ljubljana, Slovenia T +386 1 4778 100, F +386 1 4778 444, [email protected], www.siq.si Internal photos Project file: C20221443 Date: 2023-03-15 Pages: 6 Product: Wireless charger – Primary Box and Primary Pad Type reference: EOE18010815, EOE18010851 Page: 2 (6) Figure 1: Primary Box Page: 3 (6) Figure 2: Primary Box Page: 4 (6) Figure 3: Primary Pad Figure 4: Primary Pad Page: 5 (6) Figure 5: Antenna for primary pad Figure 6: Antenna for primary pad Page: 6 (6) Figure 7: PCB with radio module Figure 8: PCB with radio module
The report shall not be reproduced except in full. TN405E-03 Test report Number: T251-0030/23 Project file: C20221443 Date: 2023-01-11 Pages: 21 Product: Charger System Wireless Type reference: EOE18010815, EOE18010851, EOE18010850 Ratings: 3 x 400-480 V~; 50/60 Hz; 48 A 3Ph + PE Trademark: Applicant: Delta Energy Systems Tscheulinstrasse 21, 79331 Teningen, Germany Manufacturer: Delta Energy Systems Tscheulinstrasse 21, 79331 Teningen, Germany Place of manufacture: Delta Slovakia s.r.o. Priemyselná 4600/1, 01841 Dubnica nad Váhom, Slovakia Summary of testing Testing method: 47 CFR FCC Part 1.1307(clause (b)(1)(i)(B) and (b)(3)(ii)(B)), KDB 447498 D01 General RF Exposure Guidance v06 KDB 680106 D01 RF Exposure Wireless Charging App v03r01 Testing location: SIQ Ljubljana Mašera-Spasićeva ulica 10, SI-1000 Ljubljana, Slovenia Remarks: Date of receipt of test items: 2022-07-15 Number of items tested: 1 Date of performance of tests: 2022-07-25 - 2022-10-28 The test results presented in this report relate only to the items tested. The product complies with the requirements of the testing methods. Tested by: Luka Tosetto Approved by: Marjan Mak T251-0030/23 Page: 2 (21) CONTENTS page 1 GENERAL 3 1.1 EQUIPMENT UNDER TEST 3 2 ASSESSMENT PROCEDURE 6 3 MEASUREMENTS / CALCULATIONS 10 4 MEASUREMENT PHOTOS 11 4.1 WPT MODE 11 4.2 RFID MODE WITH WPT TURNED OFF 17 5 EQUIPMENT LIST 21 T251-0030/23 Page: 3 (21) 1 GENERAL History sheet Date Report No. Change Revision 2023-01-11 T251-0030/23 Initial Test Report issued. -- 1.1 Equipment under test Charger System Wireless Type: EOE18010815, EOE18010851, EOE18010850 Environment: Controlled / Workplace area Assessment distance: see below table with results FCC IDs: For both WPB and WPP: 2AVWKWPU30KW For WSU: 2AVWKWSU30KW Device is a wireless charger for charging of electrical forklifts. It consists of Primary Box (EOE18010815) that gets power from the grid and of Primary Pad (EOE18010851) that transfers the energy. Energy is transferred in the frequency range 55 – 65 kHz. Communication between primary and secondary pad is at 13,56 MHz. T251-0030/23 Page: 4 (21) Parts device under test consists of: T251-0030/23 Page: 5 (21) The WCS allows the user to charge the battery of industrial vehicle wirelessly by means of a magnetic field between WPP and WSU. The magnetic field which is generated and transmitted by the WPP is received by the WSU, and then converted to direct current for charging the battery. The WCS is capable of outputting up to 30 kW for battery charging. The magnetic field generated during the charging process can cause metal and other foreign objects to become hot. Therefore, it is important to keep the charging area free of foreign objects. The magnetic field is only emitted by the WPP when there is a WSU in the charging area. T251-0030/23 Page: 6 (21) 2 ASSESSMENT PROCEDURE RF EXPOSURE REQUIREMENTS according 680106 D01 RF Exposure Wireless Charging App v03r01 RF exposure must be evaluated with the client device(s) being charged by the primary at maximum output power. The RF exposure requirements must be determined in conjunction with the device operating characteristics, according to the mobile and portable exposure requirements in Sections 2.1091 and 2.1093 of the rules. RF exposure compliance is determined with respect to Sections 1.1307 (c) and (d) of the FCC rules. Evaluation is based on following conditions: field strengths do not exceed the following reference levels: - 83 V/m for the electric field and - 90 A/m for the magnetic field. Sample has been turned on with maximum power transferred between pads. While working, communication was active. Measurement distances were set as in table below under clause 3 of this report. Marking of positions is as per below pictures. Actual photo of the parts in combination with marked exposure measurement sides Left side of WPP Above WPP Right side of WPP Back of WSU Back of WPP Below WPP T251-0030/23 Page: 7 (21) Radiofrequency radiation exposure according 47 CFR 1.1307 clause (b)(1)(i)(B): With respect to the limits on human exposure to RF provided in § 1.1310 of this chapter, applicants to the Commission for the grant or modification of construction permits, licenses or renewals thereof, temporary authorities, equipment authorizations, or any other authorizations for radiofrequency sources must prepare an evaluation of the human exposure to RF radiation pursuant to § 1.1310 and include in the application a statement confirming compliance with the limits in § 1.1310. Limits: Measurement was done on WPP and WSU separately to show radiation exposure of both devices. Both were programmed to continuously work in communication mode only. Power transfer function has been disabled for this measurements, only 13.56 MHz communication was working and evaluated. Sample has been turned on with maximum power transferred between pads. While working, communication was active. Measurement distances were set as in table below under clause 3 of this report. Marking of positions is as per below pictures. Back of WPP Front of WPP T251-0030/23 Page: 8 (21) Actual photo of the part Front of WSU Back of WSU T251-0030/23 Page: 9 (21) Actual photo of the part T251-0030/23 Page: 10 (21) 3 MEASUREMENTS / CALCULATIONS Values for each configuration are listed in the following table: RF EXPOSURE REQUIREMENTS according 680106 D01 RF Exposure Wireless Charging App v03r01: Frequency (kHz) Side of the EUT and its distance to the measuring probe Maximum obtained value Limit E-field (V/m) B-field (T) H-field (A/m) E-field (V/m) H-field (A/m) 55 - 65 Left of WPP at 180 mm distance 1) 38.4 39.0 31.0 83 90 55 - 65 Right of WPP at 380 mm distance 1) 65.8 38.0 30.2 83 90 55 - 65 Back of WPP at 260 mm distance 3) 67.8 60.2 47.9 83 90 55 - 65 Back of WSU at 280 mm distance 1) 15.5 43.2 34.4 83 90 55 - 65 Below WPP at 347 mm distance 2) 75.7 41.6 33.1 83 90 55 - 65 Above WPP at 347 mm distance 2) 37.8 23.2 18.5 83 90 1) entire height was scanned…
Text truncated - open the document above for the full version.
1. PPL Specification Specifications are listed below: Number Content PPL0000 Carrier frequency shall be 13,56 MHz (13,553 ...13,567 according to ETSI EN 300 330) PPL0010 Physical layer uses 2-PSK encoding. PPL0020 Communication mode shall be half-duplex. PPL0030 Secondary side initiates data exchange to start, perform and end a charging cycle. Secondary Transmit Frame is called Communication Request. Secondary side is MASTER PPL0040 Primary side answers data exchange to start, perform and end a charging cycle. Primary Transmit Frame is called Communication Answer. Primary side is SLAVE OPTIONAL Initiation of data exchange possible from primary side. PPL0050 A loop of communication request and answer shall take less or equal 16.66 ms. PPL0060 During each loop, at least 24 bytes of Data shall be transferred in total. Either From master to Slave or From slave to Master. For Example. 12 from Slave to Master and 12 from Master to slave. PPL0070 Communication shall be robust against WPT frequency and noise caused by the WPB Inverter switching. 1 out of 60 loops may be corrupted. / (1 Fail per Second). PPL0080 Higher-level user like WSU control or WPB control are expected to be failure tolerant to 2 loops in series to be corrupted. Corruption is either request corrupt or answer corrupt. PPL0090 Communication on Master/Slave side consumes 200mW power respectively. Number Content PPL0090 Communication shall be given in this geometrical displacement of the Pads. Distance in mm. Center Position: X = 0 Y = 100 Z = 0 Extreme Positions: X = +/- 55 Y =50... 200 Z = +/- 55 PPL communication cannot be established in the range of the following geometrical displacement due to low RX-energy. Distance in mm. Disconnect Position: | 푋푋 | > 100 or Y > 300 or | 푍푍 | > 100 2. Antenna Specification Location Content WPP The creepage distances from Antenna to the Coils shall be 20mm. WSU The creepage distances from Antenna to the Coils shall be 5mm. WPP The dimension of WPP antenna is 150mmx150mm, 1-turn square coil with coil width 2mm. WSU The dimension of WSU antenna is 150mmx150mm, 2-turn square coil with coil width 2mm, spacing between tracks is 2mm. WPP and WSU Initial real impedance of antenna inside a potted pad shall not exceed 50Ω. WPP and WSU Antenna should be kept 30mm away from human body. WPP WSU Power Transfer Space WPP PPL Space If reference of WSU is inside power transfer space than power transfer is possible and efficient. WSU PPL Space is slightly bigger than power transfer space but smaller than pad size. Physical elimination of Com-conflicts. WSU Ref.
The report shall not be reproduced except in full. SIQ Ljubljana, Mašera-Spasićeva ulica 10, SI-1000 Ljubljana, Slovenia T +386 1 4778 100, F +386 1 4778 444, [email protected], www.siq.si TN405E-03 Test report Number T251-0704/22 A1 Project file: C20221443 Date: 2023-08-17 Pages: 47 Product: Charger System Wireless (30 kW PRIM BOX) and CSW 30KW PRIM PAD Type reference: EOE18010815, EOE18010851 Ratings: Input: 400 V~; 50 Hz 480 V~; 60 Hz 48 A 3Ph + Pe Trademark: Applicant: Delta Energy Systems Tscheulinstrasse 21, 79331 Teningen, Germany Manufacturer: Delta Energy Systems Tscheulinstrasse 21, 79331 Teningen, Germany Place of manufacture: Delta Slovakia s.r.o. Priemyselná 4600/1, 01841 Dubnica nad Váhom, Slovakia Summary of testing Testing method: 47 CFR Part 18 Testing location: SIQ Ljubljana Mašera-Spasićeva ulica 10, SI-1000 Ljubljana, Slovenia Remarks: Date of receipt of test items: 2022-07-15 Number of items tested: 1 Date of performance of tests: 2022-07-25 – 2022-08-04 The test results presented in this report relate only to the items tested. The product complies with the requirements of the testing methods. Tested by: Mitja Rozman Approved by: Marjan Mak T251-0704/22 Page: 2 (47) CONTENTS page 1 GENERAL 3 1.1 MEASUREMENT UNCERTAINTY 3 1.2 EQUIPMENT UNDER TEST 4 1.3 SUPPORTING EQUIPMENT USED DURING TESTING 10 2 ALL TEST EQUIPMENT AND THEIR DESCRIPTION 13 2.1 GENERAL INFORMATION 13 2.2 OTHER INSTRUMENT INFORMATION AND AUXILIARY EQUIPMENT 14 3 TEST SUMMARY 34 3.1 OPERATING VOLTAGES/FREQUENCIES USED FOR TESTING 34 3.2 TEST METHODOLOGY 34 3.3 APPLICATION OF DECISION RULE 35 4 EMISSION TESTS 36 4.1 CONDUCTED EMISSION MEASUREMENT 36 4.2 RADIATED EMISSION MEASUREMENT 37 5 PHOTOS OF THE TEST CONFIGURATION 45 T251-0704/22 Page: 3 (47) 1 GENERAL History sheet Date Report No. Change Revision 2022-12-13 T251-0704/22 Initial Test Report issued. -- 2023-08-17 T251-0704/22 A1 This test report substitutes previously issued test report T251-0704/22, dated 2022-12-13, due to amendment of the test report. Amendment of initial test report was issued due to following changes: - corrected type reference for WPP from EOE18010850 to EOE18010851 - corrected dates of calibration - added section 3.1 – operating modes 1.0 Environmental conditions: Ambient temperature: 15 C to 35 C Relative humidity: 30 % to 60 % Atmospheric pressure: 860 mbar to 1060 mbar 1.1 Measurement uncertainty The following measurement uncertainty levels have been estimated for tests performed on the product, as specified in CISPR 16-4-2 and EN 55016-4-2. This represents an expanded uncertainty expressed at 95% confidence level using a coverage factor k=2. Emission test U LAB U CISPR Conducted emission measurement (150 kHz to 30 MHz) 2.7 dB 3.4 dB Radiated emission measurement (electric field strength at an OATS or in a SAC) (150 kHz to 30 MHz) 4.8 dB / Radiated emission measurement (electric field strength at an OATS or in a SAC) (30 MHz to 1000 MHz) 5.3 dB 6.3 dB The measurement uncertainty is calculated in document EN208. T251-0704/22 Page: 4 (47) 1.2 Equipment under test Charger System Wireless (30 kW PRIM BOX) and CSW 30KW PRIM PAD Type: EOE18010815, EOE18010851 General product information Device is a wireless charger for charging of batteries with BMS. Device consists of 3 parts: - Wireless Primary Box (EOE18010815): In short marked as »WPB« - Wireless Primary Pad (EOE18010851). In short marked as »WPP« - Wireless Secondary Unit (EOE18010850). In short marked as »WSU« This test report covers Wireless Primary Box (WPB) and Wireless Primary Pad (WPP). Input / Output Ports Port No. Name Type* Cable Length / m Cable Shielded Connected during tests Comments 0 Enclosure N/E — — — / 1 AC Power input port AC / NO Connection of Primary Box to AC mains / 2 Communication between Primary box and Primary pad I/O 5 YES Connection between Primary Box and Primary Pad Feed in a single cable 3 Power transfer between primary box and Primary pad I/O 5 YES 4 Ground connection between Primary pad and Primary box GND 5 / *Note: AC = AC Power Port DC = DC Power Port I/O = Signal Input or Output Port TP = telecommunication Port GND = Grounding N/E = Non-Electrical Equipment Description Software version : V12.99 for WPB, V7.99 for WPP Hardware version : 01 for WPB, 00 for WPP One/two/three phase EUT: Three phase device Floor standing / table-top equipment or a combination: Table top (primary box), Wall mounted (primary pad) EUT Internal Frequencies Frequency (MHz) Description <108 Maximum clock frequency T251-0704/22 Page: 5 (47) Copy of marking plate The artwork below may be only a draft. The use of certification marks on a product must be authorized by the respective NCBs that own these marks. WPBA (EOE18010815): WPP (EOE18010851): T251-0704/22 Page: 6 (47) Pictures of EUT Primary box: T251-0704/22 Page: 7 (47) T251-0704/22 Page: 8 (47) Primary pad: T251-0704/22 Page: 9 (47) EUT arrangement defined by the manufacturer Drawing of EUT arrangement T251-0704/22 Page: 10 (47) 1.3 Supporting equipment used during testing List of used supporting equipment Use* Product Type Manufacturer Model Comments AE WSU Connection box Delta / Built for testing purposes. AE C…
Text truncated - open the document above for the full version.
| # | Rule Parts | Frequency Range | Power Output |
|---|---|---|---|
| 1 | 18 | 0.055 MHz - 0.065 MHz | - |

Wireless Charger Secondary Pad
Equipment Class
DXX - Part 15 Low Power Communication Device Transmitter